Reznor UDSA Gas Air Heater

UDSA Gas Air Heater – efficient to the peak

The most well-known unit from REZNOR is the gas air heater UDSA, which ensures even air distribution in industrial halls. The easy-to-install recirculation unit is available in 14 output sizes from 7 to 97 kW and consists of a heat exchanger, gas burner and a flue gas fan. The combustion air can be drawn either from outside as standard or from the showroom.

The UDSA gas air heater from REZNOR ensures even air distribution in the heated hall. Its patented heat exchanger sets new standards in terms of flow behaviour and heat transfer and ensures an efficiency of over 92 percent.

UDSA: compact, revolutionary and pioneering.
With this generation of units, halls can be heated in a particularly economical way directly – that is, without central heating – using decentrally arranged, modulating gas air heaters.

REZNOR UDSA
Gas Air Heater. The advantages:

Efficiency of more than 92%
Unit is also suitable for vertical installation
low NOx emission
innovative combustion concept
quiet operation
with CE system certification, design B or C
compact design for easy installation
even heat distribution
vertical and horizontal air deflector vanes as standard
Modulation of heating output up to 50%
EC technology
ErP Ready

These units are directly heated gas air heaters with fan-assisted atmospheric multi-gas burners.
The installation of the gas air heater, the gas and flue gas connections may only be carried out by an approved installation company.

The gas air heaters are suitable for:
- Natural gas or liquefied gas operation
- Recirculation operation
- Intake temperatures below 5°C with stainless steel heat exchanger*
- Heating operation 1-stage or 2-stage* control via room thermostat and heating control switch
- Ventilation° control via ECOtronic TN - L° with day-night weekly programme Flue gas discharge via roof, design B or C° Flue gas discharge through the exterior wall, design C°

Gas air heater type: UDSA055-4E
Gas appliance type: B22P-C12-C32-C52-C62
Country: DE
Gas category: I2ELL
Gas type: G20 Natural gas
Connection pressure: 20 mbar
Nozzle pressure: 8.40 mbar
Max. rated heat input (Hs) QN: 66.04 kW
Max. rated heat input (Hi) QN: 59.50 kW
Min. rated heat input (Hs) QN: 33.02 kW
Min. rated heat input (Hi) QN: 29.75 kW
Max. rated heat output: 54.74 kW
Min. rated heat output: 26.92 kW
Supply voltage: 230V 1N, 50Hz
Air volume flow: 5830 m3/h
Protection class: IP20
Pin No. 0461BN0677


More items - new and used - can be found in our shop!
International shipping costs on request!


Technical data

Gas air heater type: UDSA055-4E
Gas appliance type: B22P-C12-C32-C52-C62
Country: DE
Gas category: I2ELL
Gas type: G20 Natural gas
Connection pressure: 20 mbar
Nozzle pressure: 8.40 mbar
Max. rated heat input (Hs) QN: 66.04 kW
Max. rated heat input (Hi) QN: 59.50 kW
Min. rated heat input (Hs) QN: 33.02 kW
Min. rated heat input (Hi) QN: 29.75 kW
Max. rated heat output: 54.74 kW
Min. rated heat output: 26.92 kW
Supply voltage: 230V 1N, 50Hz
Air volume flow: 5830 m3/h
Protection class: IP20
Pin No. 0461BN0677

Legal information - click for details

We value your privacy
We use cookies and similar technologies on our website and process personal data of visitors to our website (e.g. IP address), e.g. to personalise content, to integrate media from third-party providers or to analyse access to our website. Data processing only takes place when cookies are set. We share this data with third parties that we name in the settings. Data processing may be carried out with consent or on the basis of a legitimate interest. Consent can be given or refused. There is a right not to consent and to change or withdraw consent at a later date. Please note our Legal disclosure and additional information regarding the use of personal data in our Privacy policy.