Masterguard A 2000 UPS
2000VA 1400W Power Supply
The uninterruptible power supply (UPS) is connected between the power supply network and the load. It protects the load from power disturbances, especially power failures.
This UPS operates on the on-line principle. This means that the connected loads are supplied via the UPS inverter. This keeps disturbances from the power supply network away, thereby increasing the operational reliability of the loads (PC, network server, multi-user systems, etc.).
In the event of a power supply failure, the built-in maintenance-free battery continues to supply the energy uninterruptedly. In practice, power failures are relatively short-lived, depending on the quality of the power supply. The energy of the UPS will therefore be sufficient to ensure continued operation of your computer system until the mains voltage returns. In the event of a prolonged power failure, you should save your data and interrupt your work.
You will be informed by the UPS acoustic (buzzer) and visual (LED) alarm that a power failure has occurred or is present. To be able to assess how urgent it is to interrupt work in the event of a prolonged power failure, the following procedures are listed to provide you with decision-making aids
| Power | 2 KVA |
| Input - Voltage | 1 N AC 230 V |
| Voltage Range | 184 V to 276 V |
| Power Factor | 0.95 |
| Battery - Integrated Type | Lead, maintenance-free |
| Battery - Voltage/V | 96 |
| Battery - Backup Time Half Load/Full Load/min | 26/10 |
| Battery - 1 Battery Extension Half Load/Full Load/min | 115/49 |
| Battery - 2 Battery Extension Half Load/Full Load/min | 215/92 |
| Output - Voltage | 1 N AC 208,220,230,240 V |
| Voltage Tolerance | ± 3% |
| Frequency on Mains Operation | see input frequency |
| Frequency at self-clocking | 50/60Hz ± 0.5% |
| Total harmonic distortion (linear/non-linear load) | max. 4% / max. 7% |
| Permissible crest factor | 3 |
| Overload capacity | 130% for 1.5 sec, 110% for 10 sec Output is short-circuit proof |
| Electrical safety | EN 50091-1 |
| Radio interference grade | EN 50091-2, Class B |
| Interference immunity | IEC 801-2,Level 4 / IEC 801-3,Level 3 IEC 801-4,Level 4 / IEC 801-5,Level 2 |
| Efficiency | > 83 % |
| Degree of protection | IP20 |
| Cooling | Fan |
For further information, the PDF document is available here
This UPS is available once without and once with batteries, please note your selection.
If you choose the product with batteries, they will be delivered with new batteries.