Item details
GHG 264 - Version with 2 auxiliary contacts (1 x normally closed; 1 x normally open)
3-pole 2 x M50 / 1 x M25
Ex safety switch 80 A
Marking according to 94/9/EC II 2 G Ex ed ia IIC T6 / II 2 D Ex tD A21 IP66 T80 °C
EC type examination certificate PTB 00 ATEX 1091
IECEx test certificate BKI 07.0010
Marking according to IECEx Ex ed ia IIC T6
Ex tD A21 IP66 T53 °C
Permissible ambient temperature -20 °C to +40 °C1)
Rated voltage up to max. 690 V
Rated current max. 80 A
Frequency 50/60 Hz
Rated making/breaking capacity AC-3 Ue 230 V / Ie 80 A
acc. to EN 60947-3 Ue 400 V / Ie 80 A
Ue 500 V / Ie 80 A
Ue 690 V / Ie 63 A
Short-circuit backup fuse up to 400 V AC: 160 A gL
up to 500 V AC: 160 A gL
up to 690 V AC: 125 A gL
Main contact terminals 2 x 25 mm2
Auxiliary/signal contact 2 x 4 mm2
Protection class I
Degree of protection acc. to EN 60529 IP66
Cable entries/housing holes M25 (d = 8 - 17 mm) see order details
M32 (d = 12 - 21 mm) see order details
M50 (d = 21 - 35 mm) see order details
Option: Metal flange with thread
Weight 6-pole approx. 9.0 kg
Housing material Glass fiber reinforced polyester
Housing color black
Auxiliary contact 1 x normally closed - delayed make; normally open - delayed break
1 x normally open - make-before-break; normally closed - break-before-make
Lockable in OFF position with up to 3 standard padlocks (Ø max. 6 mm)
New price *1,165.95 €
Legal information - click for details