Inel Klimatrol C2 Climate Monitoring Device

Technical Features

-Compact temperature and humidity monitoring device
Temperature monitoring part:
-Limit value setter for min. and max. temperature
-Optical limit value signaling by LED for
min. and max. temperature
-Limit value detection by external sensor
-Potential-free relay outputs for min. and
max. temperature
(closed when limit value is exceeded or
limit value is undershot)

Humidity monitoring part:
- -Limit value setter for min. and max. rel. humidity
-Optical limit value signaling by LED for
min. and max. rel. humidity
-Limit value detection by external sensor
-Potential-free relay outputs for min. and
max. rel. humidity
(closed when limit value is exceeded or
limit value is undershot)

External limit value input:
-Contact protection relay input for external closer
(potential-free)
-Optical display by LED
-Potential-free relay output

Fault message part:
-Optical display (green LED when no fault message
occurs)
-Output relay for immediate alarm (EPU)
-Output relay for delayed fault message (EPU)
-Alarm interval buzzer with acknowledgment button, additional
connection option for an external acknowledgment button
-Adjustable delay time for delayed
alarm message can be switched off by toggle switch
Peripherals:
-Direct connection of temperature and humidity recorders
-Direct connection of digital temperature and
humidity displays
Connection diagram

Technical Data
Rated voltage 220V 50-60Hz +lO/-15%
Limit range for: Min and Max
Temperature 0 . ..60°C
Humidity 20 . ..80% r.H.
Alarm delay 0 . ..30 minutes
Temperature outputs 1 min. and max. relay contact
potential-free (220V 500VA)
Humidity outputs 1 min. and max. relay contact
potential-free (220V SOOVA)
Immediate alarm 1 relay contact (EPU)
Delayed alarm 1 relay contact (EPU)
External output 1 potential-free relay contact
Recording output Temperature O°C = OV O,lK/mV
Humidity 0% r.H.= OV O,l%/mV
max. load 10mA
Measuring sensors FTHR or FTHK
Ambient temperature 0...50°C
Housing Plastic DIN P 30

You can find more articles - new and used - in our shop! International shipping costs on request!


Legal information - click for details

We value your privacy
We use cookies and similar technologies on our website and process personal data of visitors to our website (e.g. IP address), e.g. to personalise content, to integrate media from third-party providers or to analyse access to our website. Data processing only takes place when cookies are set. We share this data with third parties that we name in the settings. Data processing may be carried out with consent or on the basis of a legitimate interest. Consent can be given or refused. There is a right not to consent and to change or withdraw consent at a later date. Please note our Legal disclosure and additional information regarding the use of personal data in our Privacy policy.