Item details
Betschart Swiss Trafo Core Test System KPA 15
Function
The continuously adjustable output voltage, adjusted by hand using a rotary knob, is fed directly to the excitation coils of the test core.
This is intended to create a homogeneous electromagnetic field in the air gap of the test core, with which core material inserted into the air gap can be characterized.
The basic operation of the core test system is carried out via the switching and display elements on the front panel at the front of the test cart.
Technical Data
Input voltage: 2 x 400 V - 50/60 Hz
Input current: 38.3 A maximum
Output voltage: 0 ... 230 V
Output current: 65 A maximum
Measurements: Moving iron voltmeter 0 ... 500V for input voltage
Moving iron voltmeter 0 ... 250V for output voltage
Moving iron ammeter 0 ... 40/80A for input current
Moving iron ammeter 0 ... 75/150A for output current
Laboratory sockets for direct external voltage measurement, 1:1
Circuit breaker 2-pole, 63A characteristic B
Output voltage measurement
Output current measurement
Input voltage measurement
Input current measurement
Laboratory sockets for external current measurement current transformer 50A/5A
Current measurement current transformer 75A/5A output side
Main and emergency stop switch
Manufacturer's price: 27,000,-€ gross
You can find suitable regulating transformers in our shop
You can find more articles - new and used - in our shop!
International shipping costs on request!
Legal information - click for details